200KW/250KVA Biogas Generator Set 230/400V Voltage AC Three Phase
Straw Gas
TECHNICAL DATA
Genset model | SWG275 |
Genset rated power | 200KW / 250KVA |
Rated voltage | 400/230V (adjustable) |
Rated current | 360 Amps |
Frequency | 50 Hz |
Power factor | 0.8 Lagging |
Connecting type | 3 phase 4 wire |
Cooling system | Closed cycle water-cooled with fan, water tank |
Overall dimension (L×W×H) mm | 3100×1200×1800 |
Gross weight (kg) | 2300 |
Diesel Engine | |
Brand | WEICHAI |
Model | WP12D264E200NG |
Engine type | 6 cylinders in Line, 4 stroke, direct injection |
Aspiration | Turbocharged and air-to-air intercooled |
Rotating speed | 1500 RPM |
Engine cooling system | Water-cooled |
Speed governing system | Electronic speed governor |
Starting method | By 24V batteries |
Engine filter system | Dry type air filter ,fuel filter, oil filter, water filter |
Displacement(L) | 11.596 |
Bore×Stroke(mm) | 126×155 |
Compression ratio | 11.6:1 |
Ignition Order | 1-5-3-6-2-4 |
Lube capacity(L) | 27.6 |
Alternator | |
Brand | FARADAY |
Model | EG280-200N |
Excite type | Brushless self-excited AVR regulation |
Connecting type | 3 phase 4 pole |
Steady frequency change | 0.50% |
No load voltage | ≥95%-105% |
Steady voltage | ≤±1% |
Insulation class | Class H |
Protection grade | IP23 |
FEATURES
1. Deutz technology platform ,WoodWard high reliability components
and control strategy.
2. In-line, water-cooling, wet sleeve, electronically controlled
pre- mixing, sparking plug ignition,electric starting.
3. Closed-loop control and intelligent feedback make the control
more accurate.
4. lntelligent fault diagnosis,Engine safety and protection,Knock
monitoring.
APPLIED GAS:
Natural Gas, Biogas, City Sewage Gas, Landfill gas, Oil gas, farm
biogas, Coal mine gas,etc
Acceptable fuel gas pressure: 5~12kPa
CH4 content: for natural gas≥85% CH4 ,content:for biogas≥40%
Gas heat value≥5500kcal/Nm3 (23MJ/Nm3 ). Gen set output power will
increase as the gas heat value increase, if use low heat value gas
for fuel (Heat value<5500kcal/Nm3, it will lower the power
efficiency.
Gas does't include free water or free materials (the size of
impurities should be less than 5μm.)
H2S content≤200mg/NM³
NH3 content≤20mg/NM³
Impurities content≤30mg/NM³;size≤5μm
Water content≤40g/NM³, no free water.
![]() |